8 Controlling pH
The pH is controlled with the addition of CO2 gas to the system. The gas is delivered to the tank by air stone and is controlled through the Apex Controls with a solenoid valve connected to the EB832.
Once the CO2 regulator is connected to a tank, open the main tank valve.
Use the pressure adjusting screw (larger knob in front with Tunze label) to adjust the pressure (in bar) on the pressure gauge. Turning clockwise to open, thus increasing pressure, while turning counterclockwise to close, thus reducing pressure.
The pressure should be set to 0.5 up to 1 bar on the gauge (~7.5psi) - ideally 0.6 bar.
Open the fine adjustment valve (smaller valve next to the tubing connecting the regulator to the tanks) to allow gas to the tank solenoid. If the pressure on the gauge is too high this may prevent the CO2 solenoid from completely closing, which will inject excess CO2 into the system.
Programming the solenoid for a consistent pH: pH-TNK-#
- From your ApedFusion dashboard, click the icon for Outlets
- Find the gear icon in the upper right-hand corner of the Outlets page and select “Add a Virtual Outlet”
- Label the outlet to be specific for the tank and treatment for a particular time block (see example below)
Control type: pH Control
Probe name: pH
Fallback: OFF
High Value: 8.2
Low Value: 7.9
On when: HighProgramming the solenoid for diel variance:
- Using Advanced programming and Virtual outlets
- Create a unique virtual outlet for every time block which requires a different pH, and for every tank/probe which requires that pH treatment.
- Virtual Outlet Example (for the 6 hours between 6:31am and 12:30pm, the CO2 solenoid will dose CO2 into tank 1 while the probe reads 8.10 or above):
Fallback OFF
Set OFF
If Time 06:31 to 12:30 Then ON
If pH-1 < 8.10 Then OFF- Advanced Program Example (Every 6 hours, the pH setpoint changes, and each of the four time blocks has a unique virtual outlet name, as presented below in the four programming lines. The CO2 solenoid will dose the tank when the conditions of the virtual outlet program are met):
Fallback OFF
Set OFF
If Output pH_1_630 = ON Then ON
If Output pH_1_1230 = ON Then ON
If Output pH_1_1830 = ON Then ON
If Output pH_1_0030 = ON Then ON
Refer to Comprehensive Manual for set point programming.